• Simulated sine wave inverter
• Built-in AVR for voltage regulation
• Wide input voltage range: 90-280 VAC
• 24VDC
• Overload and short circuit protection
• LCD display for comprehensive information
Specifications:
• STOCK CODE: IVR-1200LBK
• DESCRIPTION: Mecer Modified Sine Wave 24VDC 1440W 2400VA Inverter
• CAPACITY: 2400 VA / 1440 W
• POWER FACTOR: 0.6
• Input Voltage range 90-280VAC
Line Mode:
• Output Voltage
• Bypass mode: 0utput voltage same as input voltage
• AVR mode: Output voltage = Input voltage 1.2 at Input voltage - Output Frequency Same as input
Battery Mode:
• Output Voltage 230Vac +/-10%
• Transfer Time 20ms typical
• Waveform Modified Sine-wave
Overload Capability:
• Bypass Mode (in VA and Watts) Load >110%+/-15% , alarm 5 mins then fault
• Load >130% +/-15%, fault immediately.
• AVR Mode (in VA and Watts)at Input voltage > 170VAC Load >100%+/-15%, go to bypass mode
• AVR Mode (in VA and Watts)at Input voltage < 170VAC Load >60%+/-15%, go to bypass mode
• Battery Mode (in W) Load>110% +/-15%, overload alarm for 15s, and then will switch to fault mode for 10s. Then unit will re-start for 5 times Load>120% +/-15% , fault & cut off O/P immediately.
Short Circuit Protection:
• Line Mode Breaker
• Battery Mode Current limit +Firmware Protection
Battery:
• Battery Voltage 24 VDC
• Acceptable Battery Type Rechargeable lead-acid battery, Deep discharge battery
• Polarity Reserve Protection Yes
• Charger available I/P range 90~280V
• BATTERY’S NOT INCLUDED
Charger:
• Constant Current Charger Voltage 28.6VDC +/-2%
• Floating Charge Voltage 27.4VDC +/-2%
• Maximum Charge Current 10A or 20A
• DC Start Voltage >22VDC
Physical:
• Dimension, D X W X H (mm) 350 x 90 x 300
• Net Weight (kgs) 5.5
Environment:
• Operating Humidity 0 to 90% Relative Humidity(Non-condensing)
• Operating Temperature 0 degrees C to 40 degrees C
• Storage Temperature -15 degrees C to 50 degrees C